·23
·
某大型商业综合楼暖通空调设计
李玲玲,徐 鸿,马友才
(中南建筑设计院股份有限公司,武汉 430070)
[摘 要
] 该项目为一类高层商业综合楼,包括公寓、还建楼、商业、写字楼、地下车库等。以该项目
的暖通空调设计为例,着重介绍了商业及办公,影院的冷热源选择和水系统设计。相关研究成果可为类似
暖通空调设计提供参考。
[关键词
] 商业综合体;冷热源;影院空调;冷却塔免费供冷
[中图分类号]
TU 8 [文献标志码]
B [文章编号] 1001
-523X
(2022
)21
-0023
-03
hVAc design of A lArge coMMerciAl coMplex Building hVAc design
Li Ling-ling ,
Xu Hong ,
Ma You-cai
[Abstract
]
The project is a first-class high-rise commercial complex, including apartments, re-construction
buildings, commercial buildings, office buildings, and underground garages. This paper takes the HVAC design
of the project as example, focusing on the selection of cooling and heating sources and water system design for
commercial, office, and cinema ,which will provide reference for the similar HVAC design.
[Keywords
]
commercial complex; cold and heat source; cinema air conditioner; free cooling by cooling tower
随着城市的经济快速发展,大型现代化商业综合
体逐渐成为当前我国城市发展的主流趋势,商业综合
体包括餐饮、购物、住宿休闲、办公娱乐等一体化的
消费服务所,不仅功能性齐全,带来了生活需求上的
便利,但是其体量大,空间多样,功能复杂,空间封
闭,人员密集,能耗大,对于暖通空调专业,提出了
更高的要求。基于武汉地区某大型商业综合体,对其
空调冷热源、空调系统设置、通风系统设计等展开分
析,重点阐述冷热源设置和节能运行措施。
1 工程简介
帝斯曼国际中心位于湖北省武汉市,总建筑面积
为 248 090 m
2,属于建筑高度超过50 m 的一类高层综
合楼,包括公寓、还建楼、商业、写字楼、地下车库
等。地下 3~5层为车库和设备用房,地下 1~2层为商
场、车库、设备用房,地上由 3栋高层组成, 1号楼为
开发住宅,共41层;2 号楼为还建住宅,共46层。3 号
楼为写字楼,共 34层,建筑高度 164.4 m;地上4号楼
为商业裙房,共6 层,建筑高度39.11 m,其中1~5层
为商场、餐饮等,6层为影院。
2 冷热源系统设计
2.1 负荷计算
经计算,各区域空调负荷见表1。
表1 空调负荷计算表
空调负荷及系统分类 冷负荷/
kW 热负荷/
kW 冷指标/
(W/m 2) 热指标/
(W/m 2) 冬季冷负荷/
kW
商业商场集中空调 11 0504 600 232 95 1 400
写字楼集中空调 6 3003 490 144 80 —
商业影院集中空调 870300213 73 —
汇总 18 370 8 390 —— 1 400
2.2 冷热源系统
本项目主要功能为商业、写字楼和影院,三者对
于空调的使用需求以及管理维护的要求均不同,根据
功能分区及业主的要求,冷热源独立设置。其中商业
和写字楼的锅炉设在地下一层锅炉房,但设备及系统
完全独立,烟囱共用。商业及写字楼的制冷机房设在
地下 5层,但设备及系统分开设置。影院则单独设置
冷热源,放置在裙房屋面。 (1)商业采用水冷离心式冷水机组作空调冷
源。其中制冷量为4 400 kW的离心式机组2 台,为满
足部分负荷的使用要求,见表2 ,同时配置制冷量
为 2 285 kW的变频调速离心式冷水机1 组台。机组
总制冷量为11 085 kW。机组的冷冻水供回水温度为
6℃/12℃,冷却水温度为32℃/37℃。 (2)商业采用燃气型真空热水锅炉2 台,作空调
热水热源。每台锅炉额定供热量为2 326 kW ,总供热
量为4 652 kW。空调供回水温度分别为6
某大型商业综合楼暖通空调设计(论文).pdf