浅 谈 医 疗 建 筑 暖 通 空 调 设 计
张 娜
(中国 中元 国际工 程有 限公 司 ,北京 100089)
[摘 要]近年来,随着我国医疗行业的快速发展,全国各地陆续新建,改建了大量医疗建筑,结合某工程案例,从 医院空
调末端形式、保证空气品质所采取措施及几个重要科室空调通风的设置等方面进行 了阐述、分析 。
[关键词 ]净化空调 ;直流式空调;通风柜;生物安全柜
[中图分类号 ]TU208 [文献标志码 ]A [文章编号 ]1001—523X (2016)064)060-02
A ir Conditioning Design of M edical Building H VAC
ZhangNa
[Abstract]In recent years,with the rapid development of China’s medical industry,a large number of medical buildings have been built or rebuilt a1l over the country.Based on some engineering case.some measures have been discussed and analyzed to ensure
the air quality considering the form of hospital air condition end as well as the setting of ventilation and air condition installed in several
important hospital departments.
[Keywords]clean air conditioning;direct air conditioning;ventilation cabinet;biological safety cabinet
医疗建筑空调系统不同于一般建筑的空调系统,需综合
医院特点及各种因素来考虑空调、通风系统的设置,要求医
院暖通设计人员要对医院各科室使用流程 ,工艺要求等进行
多方面调查 、研究,在空调,通风设计 中合理设计,满足不
同类型科室的空调需求,合理有效及时排出污染气体 ,避免
医院内部交叉感染。保证具有放射性辐射房间的安全性 、稳
定性及设置必要的应急措施等。以下根据医院建筑特点结合
北京某医院的设计实例,探讨了暖通空调系统设计。
1 医院空调末端形式
医院的空调末端形式繁多,系统复杂 ,在空调系统划分
时应根据各科室的使用特点 ,对于具有严重污染或有洁净要
求的房间单独设置空调系统或送排风系统。
1.1 全空气净化空调系统
医院的很多区域均有洁净要求 ,如中心供应无菌区、输
液配置中心 (其中,抗生素配置为直流式 )、生殖中心、介
入治疗 、手术部、血液病房等 ,为控制病源降低交叉感染的
风险,这些区域采用独立的净化空调系统 ,净化空调系统新
风进行集中预处理,采用粗效 、中效、高中效三级过滤。
(1)输液配置中心、成 品存放及成品发放按Ⅲ级洁净辅
助用房设计,设置净化空调系统,送风量为 13次 m,气流组
织为高效送风口均匀上送,单层竖向百叶均匀下回。 ’
(2)中心供应的无菌区和无菌品库房按 Ⅲ级洁净辅助用
房设计,设置净化空调系统 ,送风量分别为 13次 /h,气流组
织为高效送风口均匀上送 ,单层竖向百叶均匀下回。
(3)洁净手术部包括 I级洁净手术室 ,Ⅲ级洁净手术室
及正、负压切换手术室。每问手术室设一个净化空调系统。
I级洁净手术室送风量按手术区工作面高度截面平均风速
v=O.25m/s计算 ,气流组织为手术室专用送风单元集中上送 ,
双侧单层竖向百叶下回。
Ⅲ级手术室送风量 为 18次 /|l,气流组织为手术室专用送
风单元集中上送,单层竖 向百叶下回,其 中正 、负压切换手
术室为直流式,采用变频排风机,排风机设在屋顶。排风机
低速运行时为正压状态 ,排风机高速运行时为负压状态。
体外循环、无菌敷料按 Ⅱ级洁净辅助用房设计 ,送风量
为 12次 /h;洁净走廊、术后苏醒、辅助区按 Iv级洁净辅助
用房设计,送风量