第一章:施工用电
序号 常见隐患类别 危险等级序号 常见隐患类别 危险等级
1电源线拖地、泡水,未绝缘悬挂 A级 10配电箱缺少线路图 C级
2电缆线敷设无保护措施 A级 11
配电箱电工未每日巡检,缺少巡检
记录表或巡检滞后
B级
3电源线胶皮破损未绝缘包扎 A级 12配电箱内接线一闸多机 A级
4违规使用两芯线、花线 A级 13配电箱接线端子无防护和线路标识 B级
5违规使用多项插头、家用插板 A级 14用电设备接线时未接PE线 A级
6非电工接电(未持证上岗) A级 15
配电箱无箱门、箱门与箱体未做跨
接
A级
7用电设备与开关箱距离超过3m A级 16
配电箱内有杂物,或配电箱周边堆
放较多杂物
B级
8配电箱未可视化验收 C级 17用电设备直接接二级箱用电 A级
9配电箱内元器件歪斜和松动 B级 18
用电设备接入漏保上端,未经过漏
电保护器
A级
2
问题描述
:①现场临时用电使用的电源线拖地、泡
水。
整改措施:
①制作加工绝缘挂钩支架,对拖地电源
线进行绝缘悬挂处理。
原因分析:
①现场临电交底不到位,施工过程中巡
查不到位
管控措施:
①临电施工前,进行专项交底,要求劳
务队进场时加工制作。
3
问题描述:
①电缆线敷设过路无保护。
整改措施:
①在非过路要求电缆线沿地面敷设须订
方木盒保护,并刷警示油漆;②对无条件架空或埋地
时,可采用带线槽减速带对电缆进行保护。
原因分析:
①作业人员安全意识低;②检查不全面,
责任单位未对临电隐患引起足够重视。
管控措施:
①加强临电使用危害类教育;②对现场临
电安全进行全面排查,加强日常管理;③制定合理的
防护方案并交底到位。
4
问题描述:
①使用两芯线;②电源线接头处未绝缘
包扎。
整改措施:
①淘汰两芯线,采用合格的三芯线并规
范接线;②对接头处电源线采用绝缘胶带包扎。
原因分析
:①分包单位无专业电工;②项目对劳务
分包临时用电交底、验收不到位。
管控措施:
①要求劳务单位配备专职电工;②加强
对劳务分包临时用电的交底和验收工作巡查力度;③
对不合格电缆及时清退出场。
5
问题描述:
①违规使用淘汰的多向插头;②违规使
用家用插座。
整改措施:
①更换使用合格的移动式开关箱;②现
场电动工具更改为充电式电动工具。
原因分析:
①作业人员对安全用电意识淡薄,仍然
使用淘汰的用电产品和不合格开关箱;②电工现场巡
查不到位,项目责任工程师监督不到位。
管控措施:
①加强对作业人员临时用电的安全教育
和交底;②加强电工现场安全用电巡查的监督,推广
使用手持充电式电动工具。
6
问题描述:
①无证普工进行接电、维修操作。
整改措施:
①立即制止该作业人员的违规行为,并
对作业人员进行安全用电教育;②安排持证的电工进
行接电、维修操作。
原因分析:
①作业人员安全意识低,为图方便,私
自进行接电、维修;②项目持证电工配备不足,对作
业人员安全用电教育交底不到位。
管控措施:
①要求分包队伍配备持证电工;②持证
电工接受项目统一管理,负责用电的
中建机电安装项目安全隐患识别2021(84页)